A fire door spends nearly all of its life doing nothing. On the one occasion it is called upon, it must close without assistance and remain closed. Everything about its selection, installation, and upkeep is directed to that single moment.

(000) 000-0000
Rolling steel shutter along a commercial corridor
Inspector with a tablet checking a rolling steel door
Governing standard
NFPA 80
Testing
At installation and annually
Records
Written and retained

What a fire door is for

Building codes divide larger buildings into compartments by means of fire-rated walls, so that a fire beginning in one part is contained for a period, and occupants have time to leave and firefighters time to work. Wherever such a wall has an opening, the opening must be protected by an assembly of comparable resistance. A fire door is that assembly.

It should be understood from the outset that this is a regulated matter. The requirement for a fire door, its rating, and its location are determined by the building code and by the authority having jurisdiction, which is to say the local building official or fire marshal. The architect or engineer of record specifies the opening. Our part is to supply a door that meets the specification, install it in accordance with its listing, test it, and document the result. We do not decide where a fire door is needed, and we would not advise an owner to rely on a door supplier for that judgment.

Rolling steel fire doors

The overhead fire door in commonest use is the rolling steel type. A curtain of interlocking steel slats coils about a barrel within a steel hood above the opening and runs in steel guides fixed to the wall at each side.

It differs from an ordinary rolling service door in several respects.

  • It is a tested and labeled assembly. The curtain, guides, hood, bottom bar, and release mechanism have been tested together by a recognized laboratory, and the door bears a label stating its rating.
  • It closes automatically. A release device disengages the door from its operator or holding mechanism, and the door descends under its own weight.
  • Its descent is governed. A speed-limiting governor keeps the closing speed within prescribed limits, so that the door neither slams nor stalls.
  • Its guides and fixings are designed for fire. They allow for expansion of the steel and are attached to the wall in the manner the listing prescribes.

Fire-rated counter shutters are smaller doors of the same kind, used over service counters, pass-throughs, and concession openings in rated walls.

Insulated fire doors, with mineral wool in the slats, are available where the transmission of heat or sound across the opening is also a concern. Doors may additionally carry a smoke rating where the code requires it, in which case they are fitted with perimeter gaskets.

Ratings

Fire doors are rated by the length of time for which the assembly withstood the standard fire test.

Rating Typical application
4 hour Openings in walls separating buildings or dividing a building into fire areas
3 hour Openings in walls of similar function, as specified
1 1/2 hour Openings in two-hour enclosures, such as shafts and exit stairs, and some exterior walls
3/4 hour Openings in one-hour corridor and room partitions, and some exterior walls

The rating required follows from the rating of the wall and the nature of the opening. It is a matter for the designer and the code official.

On the one occasion a fire door is called upon, it must close without assistance and remain closed.

How the door is released

A fire door must close when there is a fire and at no other time, and it must do so whether or not anyone is present. Several means are used.

Fusible links. The traditional method. A link of two pieces of metal joined by a low-melting solder holds the release mechanism by a chain or cable. At a set temperature, commonly 165 degrees Fahrenheit, the solder melts, the link parts, and the door closes. Links are simple and need no power. They respond only when hot gases reach them, which may be late in the development of a fire.

Electromechanical release devices. These hold the door open while energized and release it on a signal from the building’s fire alarm system or a local smoke detector. The door thus closes at the first detection of smoke. Most have a time delay and battery support to prevent release on a brief loss of power.

Motor-operated fire doors. Operators designed for the purpose close the door under power on an alarm signal, and by gravity if power is lost. Some provide for the door to stop on meeting an obstruction and then resume closing.

Fusible links are generally retained as a backup even where an electrical release is fitted. The connection to the fire alarm system is coordinated with the alarm contractor.

Before and after

A rolling grille and a solid rolling steel door

The first image shows an open rolling grille with louvered panels above it. A grille secures an opening while allowing air and sight to pass. It offers no resistance to fire or smoke, and it would not be acceptable in a rated wall.

The second image shows a solid rolling steel door closed across a service entrance, with clearance signs posted at the head. Where an opening in a fire-rated wall requires protection, the work consists of fitting a labeled rolling steel fire door to the manufacturer’s listing, connecting its release, and drop testing it. The owner then has an opening that will close of its own accord in a fire, and a record to show that it has been tested.

BeforeBefore: Dark rolling grille with louvered panels above
AfterAfter: Rolling steel door with clearance signage on a service entrance
Illustrative comparison using licensed stock photography. It shows the kind of change this service makes and is not a documented customer project.

Installation

A fire door is rated as installed. A labeled door fixed to the wrong construction, or with the wrong fasteners, or with its guides improperly spaced, is not a rated assembly, whatever its label says. The work must follow the manufacturer’s installation instructions exactly.

  1. Verification of the opening. The wall construction, the dimensions, and the condition of the jambs and head are checked against the door’s listing. Rolling fire doors are listed for particular wall types.
  2. Mounting the guides. With the specified fasteners at the specified spacing, and with the clearances the listing requires for expansion.
  3. The barrel, curtain, and hood. Assembled and tensioned.
  4. The governor and release mechanism. Installed and adjusted.
  5. Release devices. Fusible links are positioned as prescribed, on both sides of the wall where required. Electrical release devices are connected and tested with the alarm contractor.
  6. The drop test. The door is released and allowed to close fully under its own weight. Its closing speed is measured against the limits in the standard. The door is then reset, and the test is repeated to confirm that it was reset correctly.
  7. Documentation. A written record of the installation and the test is given to the owner.

Inspection and annual testing

The standard that governs fire doors, NFPA 80, requires that rolling steel fire doors be inspected and tested at the time of installation and at least annually thereafter, and that a written record be kept for the authority having jurisdiction. Doors should also be tested after any repair or alteration.

The annual procedure includes the following.

  • Visual inspection of the curtain, bottom bar, guides, hood, and fixings for damage, missing parts, and field modifications
  • Confirmation that the label is present and legible
  • Inspection of fusible links, chains, and cables, and replacement of any link that is painted, corroded, or damaged
  • Confirmation that nothing obstructs the opening or the path of the door
  • A drop test, with the closing speed observed
  • Resetting of the door and a second drop test
  • A test of any electrical release from its initiating device
  • A written report

A fire door that has not been tested within the past year may not be compliant, and a door that fails to close on test will not close in a fire. Annual testing is the most neglected obligation attached to these doors, and we would encourage any owner who is uncertain of the date of the last test to arrange one.

What goes wrong

The faults we find on inspection are remarkably consistent.

Obstruction. Goods stacked in the doorway, conduit or pipework run through the guides, or racking built across the path of the curtain.

Painted or missing links. Paint insulates a fusible link and delays its release. Links are sometimes removed or wired up by those annoyed at accidental drops.

Improper resetting. After a drop, whether from a test or by accident, the door has been raised but the release mechanism or spring tension has not been correctly restored.

Damage. Bent slats or guides from vehicle impact, which can prevent the curtain from descending.

Unlisted modifications. Holes drilled in the curtain, attachments to the bottom bar, or operators fitted that are not part of the listing.

Corrosion. In damp or unheated locations, and where road salt reaches the lower guides.

Considerations in this climate

Fire doors in unheated buildings and on exterior openings are subject to the same conditions as any other door in Wisconsin. Lubricant in the barrel bearings and governor stiffens in the cold, and a door that closes within the permitted speed in summer may be sluggish in January. Condensation promotes rust on links and chains. Ice at the sill may prevent the bottom bar from seating. An annual test conducted in the colder months gives the more searching result.

Fire doors are often installed alongside doors of other kinds in the same building: insulated sectional doors on the exterior, and high-speed doors at busy interior openings. Where an opening needs both fire protection and frequent access, a fire door that normally stands open is commonly paired with a separate working door. The general course of a commercial project is set out under commercial garage door installation.

Questions and answers

Questions about commercial fire doors

How often must a rolling fire door be tested?

NFPA 80 calls for inspection and testing at installation and at least once a year, with a written record retained.

What is a drop test?

The door is released as it would be in a fire and allowed to close under its own weight. The closing speed is checked, the door is reset, and the test is repeated.

Who decides whether a fire door is required?

The building code, as applied by the designer and the local authority having jurisdiction. We install and test to their specification.

Can a fire door be used as an everyday door?

It can, if it is specified for that use and fitted with a suitable operator. Many are left open and close only on alarm.

Why must fusible links not be painted?

Paint insulates the link and can delay or prevent its release. Painted links should be replaced.

What happens after a fire door has dropped?

It must be reset by someone who understands the mechanism, and then tested again. An incorrectly reset door may not close the next time.